Journal Search Engine
Download PDF Export Citation Korean Bibliography PMC Previewer
ISSN : 1229-6783(Print)
ISSN : 2288-1484(Online)
Journal of the Korea Safety Management & Science Vol.16 No.2 pp.167-174
DOI : https://doi.org/10.12812/ksms.2014.16.2.167

대학교 강의실 EHP 제어를 이용한 에너지 절약 시스템

정 기 범*
*유한대학교 건축설비과

Energy Saving System of EHP Control at the College Lecture Room

Kybum Jeong*
*Dept. of Building Services, Yuhan University
Received March 12, 2014; Revision Received June 20, 2014; Accepted June 20, 2014.

Abstract

Heating and air conditioning system is changing rapidly from the traditional HVAC central supply system tothe individual supply system with electrical heat pump system (EHP) in Korean school buildings. Theindividual supply system has advantages to turn on and off individually and to adjust the thermal comfortseparately, but energy is wasted in the unoccupied classroom when the last leaving occupant does not turn offthe controller. If the controller is to be off automatically while the classroom is not in use, energy consumptionwould decrease dramatically.This project aims to cease the unnecessary EHP supply in vacant classroom by inputting the class schedulefrom the central control room to reduce the energy-spending. Experimental measurements were carried outbetween the controlled classroom that is turned off when not in use and the uncontrolled room that is turnedon continually. Occupant’s comfort and energy consumption were measured and compared between thecontrolled case and the uncontrolled case.The energy consumption of controlled classroom case is 30-60% less than that of the uncontrolled classroomcase. This result shows that controlling the cooling supply for the unoccupied classroom using the classschedule can decrease the energy consumption remarkably. This supply control system can be used to conserveenergy in school structures like universities.

 

Reference

1.Kim, Y.(2008) "The Economic Comparison of EHP and GHP for Medium Capacity Air-conditio ning", Journal of SAREK, Vol. 20, No. 3, pp. 167∼174.
2.Kim J.Y., Park, H.S., Kim, S.S., Suh, S.J. (2009) "A Study on the Application Plan of Air-Conditio ning and New and Renewable Systems in the Large High Schools", Journal of SAREK, Vol. 21, No. 10, pp. 564∼574.
3. Park, K.H., KIm, S. (2012) "The Economic Effe cts and Operating Characteristics of the Outdoor Unit in Accordance with Zoning Plan of Gas Engine Driven Heat Pump Installed in the Univer sity Building", Journal of SAREK, Vol.24 No.1, pp. 70∼76.
4. Park, K.H., Kim, S. (2011) "Analysis of Energy Consumption of Buildings in the University", Journal of SAREK, Vol.23 No.9, pp. 633∼638.
5. Lee, H.Y., Chang, H.J. (2012) "A Study on the Improvement of Indoor Thermal and Air Environ ment Made by Ceiling Cassette Type Cooling and Heating Unit in Classrooms", Journal of KSES, Vol. 32, No. 6, pp. 141-148.
6.Shin, G.W., Kim, G.T., Joo, H.Y., Lee, J.K. (2006) "Economic Analysis of Heat Pump System through Actual Operation", Proceedings of the SAREK SAM, pp. 921∼926.
7.Lee, Y.J., Jeong, J.H., Song, D.S. (2010) "Examin ation on the operational characteristics of the sys tem air conditioners during the heating", Procee dings of the SAREK SAM, pp. 169-174.
8. Kim J.Y., Park, H.S., Hong, S.H., Kim, S.S., Hur, I.K., Suh, S.J. (2009) "A Study on the Appli cation Plan of Air-Conditioning and Renewable Complex Systems in the Small Schools", Procee dings of the SAREK SAM, pp. 946-951.